INSTALLATION INSTRUCTIONS

95- 6940- 12

L8148A,E,J

Aquastat® Relays

APPLICATION

The L8148A,E,J Aquastat® Relays are immersion-type 

control ers for use with forced hydronic heating systems. 
The combination high limit and intermediate switching 

relay works with a low voltage (24V) thermostat to control 
burner and circulator circuits. A call for heat by the 

thermostat starts both the burner and the circulator. 
When boiler-water temperature exceeds the high-limit 

settings, the burner circuit is broken; the circulator 
continues to operate during the thermostat call for heat.

The L8148A controls line-voltage burner circuits; the 

L8148E,J control low-voltage burner circuits; the L8148J 
controls millivoltage burner circuits. All models control 

line-voltage circulator circuits.

L8148A,E,J have provisions for adding low-limit 
control ers; L8148E,J can power valves in multizone 

systems.

L8148E is available with a plug and 50 VA transformer for 
use with Honeywel  Smart Valve SV9500/SV9600.

SPECIFICATIONS

Electrical Ratings:

Table 1. Circulator Control Circuit (A):

Table 2. Burner Control Circuit:

Scale Range: 140°F to 240°F (60°C to 116°C) or 180°F 

to 240°F (82°C to 116°C).

Differential: Nonadjustable.

High Limit Dial Stop: Adjustable.

Maximum Pressure on Immersion Well: 255 psi (1758 

kPa).

Maximum Ambient Temperature: 150°F (66°C) with 

1.2A, 24V load; 77°F (25°C) with 1.4A, 24V load.

Maximum Bulb Temperature: 40°F over setpoint, up to 

265°F (4°C over setpoint, up to 129°C).

Thermostat Heat Anticipator Setting: 0.2A.

Material Safety Data Sheets (MSDS): For information 

on heat-conductive compound, see form number 
69-0955.

INSTALLATION

When Installing This Product…

1. Read these instructions careful y. Failure to fol ow 

them could damage the product or cause a 
hazardous condition.

2. Check the ratings given in the instructions and on 

the product to make sure the product is suitable for 

your application.

3. Installer must be a trained, experienced service 

technician.

4. After installation is complete, check out product 

operation as provided in these instructions.

WARNING

Explosion Hazard.
Can cause severe injury, death or property 

damage.
This product is intended for use only in systems 

with a pressure relief valve.

Type

120 Vac

240 Vac

Ful  Load

7.4

3.7

Locked Rotor

44.4

22.7

Model No.

Voltage

Electrical Rating

L8148A

Line

Same as circulator control 

circuit.

L8148E,J

Low

0.8A maximum at 24 Vac.