GE BoxTimer GE Time Switch (15251, 15252 and 15253) Quick Start Manual

GE Timers Quick Start Manual - BoxTimer GE Time Switch (15251, 15252 and 15253).
Download
Page  of 2
4.7, 1328 votes
background image

SPECIFICATIONS

Input Voltage: 120 VAC, 208/240 VAC, or 277 VAC in all units based upon 
dipswitch configuration.

15252

NEMA3R Indoor&Outdoor BM-A301US5-O2

15253,15251

NEMA1 Indoor

BM-A301US5-I2

15250

NEMA3R Indoor&Outdoor EM-A301US9-O2

SwitchRating:DPDTModels

NormallyOpenContacts

40A Resistive, 120-277Vac.
30A General Purpose, 120-277Vac.
20A Resistive, 30Vdc
1 HP, 120Vac ; 2HP, 240Vac
20A Ballast, 120-277Vac.
15A Tungsten, 120Vac
800VA, Pilot Duty, 120Vac.
720VA, Pilot Duty, 240Vac.
TV-5, 120Vac

NormallyClosedContacts         

30A Resistive, 120-277Vac
15A General Purpose, 120-277Vac
15A Resistive, 30Vdc
20A Ballast, 120-277Vac
1/4HP, 120Vac; 1/2HP, 208-240Vac.
290VA, Pilot, 120Vac.
360VA, Pilot, 208-240Vac.

NOTE: If loads are connected to both NC and NO contacts, both contacts are 
derated to 67% of the above values.

ENVIRONMENTALRATINGS

Ambient Temperature: –40F to 130F
Humidity: 0-95% RH, Non-condensing

WIRINGCONNECTIONS

Screw clamp terminals for up to 2 AWG #8 wires  
per position. For supply connections, use 8AWG or larger wires suitable for at 
least 105° C. Use copper conductors only.

LIGhTS

Power LED (Orange) – Light illuminates when power is applied to  
the timer
Status LED (Green) – Light illuminates when power is applied to load.

INSTALLATION

CAUTION:  Before wiring or service, power to this time switch and  the 
equipment it controls must be turned off. Turning off the timer switch only 
will not prevent a shock hazard. Replace cover plate within housing before 
supplying power to time switch. Installation should be performed by a licensed 
electrician only. Before installing this product read all instructions carefully.
Remove protective cover panel within time switch housing by removing 
screws located above timer face and at the bottom of the cover panel.

DIPSWITChCONFIGURATION

WARNING: Failure to properly configure the dipswitch will result in 

damage to the unit and void the warranty! Before installing and wiring the GE 
Time Switch, proper configuration must be selected. This is accomplished as 
follows:

INPUTVOLTAGEDIPSWITChSETTING: 

1. 

Do not apply power to the timer prior to setting correct Input Voltage DIP 
switch.

2. 

Determine the input voltage which will be applied to the timer (i.e. L1 and 
L2/N terminals, see wiring diagrams)

3. 

Set the DIP switch according to the diagram below.

NOTE: Unit is shipped with DIP switches set for 277VAC Input Voltage

CAUTION: Do not check circuits by “sparking” wires to terminals. Damage to 
the timer may result.

NOTE:For outdoor locations (model GE 15252), rain tight or wet location 
conduit hubs that comply with requirements of UL 514B (standard for fittings 
for conduit and outlet boxes) must be used.

1. 

Remove 2 screws retaining the interior cover panel and remove panel 
by prying out with a thin blade at the top.. Select knockouts to be used. 
Remove the inner 1/2” knockout by inserting a screwdriver in the slot 
and carefully punch knockout loose. Remove slug. If the 3/4” knockout 
is required, remove the outer ring with pliers after removing the 1/2” 
knockout. Smooth edges with knife if necessary.

2. 

Place enclosure in desired mounting location and mark the three 
mounting holes.

3. 

Drill holes for #10 screws, start screws in holes.

4. 

Place enclosure over screws and tighten screws.

5. 

Connect conduit hubs to conduit before connecting the hubs to the 
enclosure. After inserting hubs into enclosure, carefully tighten hub lock 
nut. Do not over-tighten.

DipswitchSettingcontinued:
6. 

Install in accordance with all applicable National and Local code 
requirements. See Figure 1 and wiring diagrams.

7. 

Replace interior cover panel and 2 screws.

TimeSwitch

15251/15253 

Indoor 

NEMA 1-Rated Enclosure 

15252 

Indoor/Outdoor 

NEMA 3R-Rated Enclosure

120VAC

277VAC (Default)

208~240VAC

NOTE: Unit is shipped with DIP Switches set for 277VAC Input Voltage. 

CAUTION: Do not check circuits by “sparking” wires to terminals. Damage to

the timer may result.

 

INPUT VOLTAGE DIP SWITCH SETTING:
1. Do not apply power to the timer prior to setting correct Input Voltage DIP switch.
2. Determine the input voltage which will be applied to the timer (i.e. L1 and L2/N terminals,

see wiring diagrams).

3. Set the DIP Switch according to the diagram below.