INSTALLATION INSTRUCTIONS

66-1153-03

R7140G,L,M

Burner Control Modules

APPLICATION
The Honeywell R7140G,L,M Burner Control Modules are 

microprocessor-based integrated burner controls for 

automatically fired gas, oil or combination fuel single burner 

applications. The Burner Control Module system consists of a 

Relay Module, Q520A Subbase, Amplifier and Purge Card. 

Options include S7800 Keyboard Display Modules (KDM).

The R7140 Burner Control Modules directly replace many 

BC7000 PM720G,L,M, and many R4150G,L,M and 

R4140G,L,M units using the existing Q520A 20-terminal 

Wiring Subbase.

The R7140 can be demonstrated or tested on the FSP5004 

tester. Note that the R7849 UV Amplifier or the R7851 Optical 

Flame Amplifier cannot be tested.

The R7140G,L,M is programmed to provide a level of safety, 

functional capability and features beyond the capacity of 

conventional controls.

Functions provided by the R7140G,L,M include automatic 

burner sequencing, flame supervision, system status 

indication, system or self-diagnostics and troubleshooting.

FEATURES
• Device status available to ModBus™ through S7810M 

card or S7800A1001 Series 5 Keyboard Display.

• Safety features:

— Interlock check.

— Closed loop logic test.

— Dynamic AMPLI-CHECK™.

— Dynamic input check.

— Dynamic safety relay test.

— Dynamic self-check logic.

— Expanded safe-start check.

— High Fire Purge Switch test (R7140L only).

— Internal hardware status monitoring.

— Low Fire Start Switch test.

— Tamper resistant timing and logic.

• Application flexibility.
• 0.8 or 3.0 second Flame Failure Response Time (FFRT), 

depending on amplifier selected.

• Dependable, long-term operation provided by 

microcomputer technology.

• Five LEDs for sequence information. See Fig. 1.
• Five function Run/Test Switch.
• Interchangeable plug-in flame amplifiers.
• Nonvolatile memory; history files and sequencing 

status are retained after loss of power and can be 

viewed using the Keyboard Display Module 

S7800A1001 (sold separately).

• Report generation (optional) through modbus™.

NOTE: Check Service Notes on page 7 and Static Check-

out on page 26 prior to installation of R7140.

• Burner controller data (optional):

— Lockout/alarm status.

— Total cycles of operation.

— Total hours of operation.

• Status of configuration jumpers.

• Status of Run/Test Switch.