EN0C-0741 0599R2-MA

XLS-278 and XLS-270

Manual Pull Stations

SPECIFICATION DATA

DESCRIPTION

The XLS-270 and XLS-278 series Manual Pull Stations are
part of Honeywell's Signature Series system. The XLS-270
Fire Alarm Manual Pull Stations feature a "teardrop" shape.
They are made from die-cast zinc and finished with red epoxy
powder-coat paint complemented by aluminum colored
stripes and markings.

With positive pull- lever operation, one "pull" on the station
handle breaks the glass rod and turns in a positive alarm,
ensuring protection plus fool-proof operation. Pre-signal
models (XLS-270P) are equipped with a general alarm (GA)
key-switch for applications where two-stage operation is
required. The "up-front" highly visible glass rod discourages
tampering.

Honeywell's double action single stage XLS-278 station is a
contemporary style station made from durable red colored
Lexan. To initiate an alarm, first lift the upper door marked
"LIFT THEN PULL HANDLE", then pull the alarm handle.

FEATURES
•  Single stage double action XLS-278 features a rugged

Lexan housing

 

•  XLS-270 models have traditional familiar appearance

 

•  XLS-270 models are available for one stage (GA),

two stage (pre-signal), and double action

 

•  Break glass operation on XLS-270 models

 

•  Intelligent device with integral microprocessor

 

•  Non-volatile memory

 

•  Automatic device mapping

 

•  Electronic addressing

 

•  Stand-alone operation

 

•  Diagnostic LEDs

 

•  Designed for high ambient temperature operation

 

•  Designed to ISO 9001 standards

The integral microprocessor built into each Signature Series
station provides four important benefits: Self-diagnostics and
History Log, Automatic Device Mapping, Stand-alone
Operation and Fast, Stable Communication.

Self-Diagnostics and History Log:

Each Signature Series manual station constantly runs self-
checks to provide important maintenance information. The
results of the self-check are automatically updated and
permanently stored in the station's non-volatile memory. This
information is accessible for review any time at the control
panel, PC, or by using the SIGA-PRO Signature
Program/Service Tool.

The information stored in the station's memory includes:
- Station serial number, address, and station type.
- Date of manufacture, hours of operation, and last

maintenance date.