Trane Voyager 12.5 to 25 Tons Quick Reference Guide
January 2015
RT-PRC038G-EN
© 2015 Trane All rights reserved
1
2
Quick Reference Guide
Voyager™
12½-25 Ton Packaged Rooftop Units
Cooling & Gas/Electric
Table 1.
Model number description
T*D
Cooling Only (Electric Heat Optional), Downflow
T*H
Cooling Only (Electric Heat Optional), Horizontal
Y*D
Gas Heat Unit, Downflow
Y*H
Gas Heat Unit, Horizontal
* Standard (S) or High (H) Efficiency
Table 2.
List of factory installed options (FIOPs)(a)
(a) Most Factory Installed Options are available for downflow air discharge units only. Verify with ordering system
for availability.
2” MERV 8 or MERV 13 Pleated Filters w/ Removal Tool Horizontal Side Access with Disconnect Switch
BACnet™ Communication Interface (BCI)
LonTalk® Communication Interface (LCI)
Barometric Relief(b) (c)
(b) Requires an Economizer.
(c) Some field set up required.
Modulating Gas Heat Furnace w/ a 2.5:1 Turndown Ratio(d)
(d) Requires ReliaTel Options Module.
Clogged Filter/Fan Failure Switch(d)
Motor Shaft Grounding Ring(e)
(e) Available with Two Speed Fan or Variable Speed Fan.
Complete Coat™ Microchannel Condenser Coil
NOVAR Return Air Sensor
Condensate Overflow Switch
NOVAR Unit Controls (3051 and 2024)
DCV Harness
Oversized Motors
Dehumidification
Powered/Unpowered Convenience Outlet(f)
(f) Must be ordered with Through the Base Electrical option or Horizontal Side Access, and either Unit Mounted
Disconnect switch or Circuit Breaker.
Delivered VAV(d)
Stainless Steel Drain Pan
Discharge Air Sensing Kit(d)
Stainless Steel Heat Exchanger
Economizer - Low Leak/Downflow(c)
Supply & Return Air Smoke Detectors(d)
Economizer - Standard/Downflow (c)
Through the Base Electrical with Circuit Breaker
Electric Heaters
Through the Base Electrical with Disconnect Switch
Fault Detection & Diagnostics (FDD)
Through the Base Gas Provision
Frostat™(d)(g)
(g) Standard on high efficiency units.
Tool-less Hail Guard
High Efficiency Motors
Trane® Communication Interface (TCI)(h)
(h) TCI is for use with non-VariTrac™ systems and VariTrac systems.
High Short Circuit Current Rated (SCCR) Electrical
Subsystem(i)
(i) Available on 208 V/60 Hz, 230 V/60 Hz, and 480 V/60 Hz only.
Two Speed Fan Provision
Hinged Access Panels
Variable Speed Fan Provision for Single Zone VAV
Horizontal Side Access with Circuit Breaker
Table 3.
12½-25 ton packaged rooftop performance data (gas or electric heat)
Standard Efficiency
High Efficiency
Nominal Size (Ton)
12.5
15
17.5
20
25
12.5
15
17.5
20
25
Cooling Performance
Nominal Airflow CFM / ARI Rated CFM
5,000/4,400
6,000/5,300
7,000/6,125
8,000/7,000
10,000/8,000
5,000/4,000
6,000/5,250
7,000/5,600
8,000/6,400
10,000/8,000
Tot / Sens Cap (MBh)(a) (b)
(a) Cooling performance is rated at 80/67/95 & 400 cfm/ton.
(b) Short orifice metering device.
150.1/116.0
186.1/139.1
210.3/165.0
258.9/197.3
296.4/228.4
149.6/113.4
181.5/138.0
212.7/165.5
259.0/192.5
295.3/234.2
EER(c)
(c) EER is rated at ARI conditions and in accordance with ARI standard 210/240 or 340/360.
11
11
11
10.0
10.0
12.1
12.1
11.8
11.0
10.6
IEER (One Speed Fan / Multi or Variable
Speed Fan)(d)
(d) Integrated Energy Efficiency Ratio (IEER) is rated in accordance with AHRI standard 210/240 or 340/360.
12.2/13.5
12.2/13.2
11.8/12.9
11.5/12.3
10.4/12.0
13.5/15.0
14.0/15.0
13.0/14.0
12.4/14.0
12.4/15.0
Gas Heating Performance(e)
(e) Verify option availability in product data catalog.
Low Heat (Input/output) - (MBh)
150.0/122.0
250.0/203.0
250.0/203.0
250.0/203.0
250.0/203.0
150.0/122.0
250.0/203.0
250.0/203.0
250.0/203.0
250.0/203.0
Medium Heat (Input/output) - (MBh)
350.0/283.5
350.0/283.5
350.0/283.5
350.0/283.5
350.0/283.5
350.0/283.5
350.0/283.5
350.0/283.5
350.0/283.5
350.0/283.5
High Heat (Input/output) - (MBh)
250.0/203.0
350.0/284.0
350.0/284.0
400.0/324.0
400.0/324.0
250.0/203.0
350.0/284.0
350.0/284.0
400.0/324.0
400.0/324.0
Other Information
Net Weight (Lbs) - Gas Heat
1508
1925
2007
2069
2054
2207
2176
2140
2211
2245
Net Weight (Lbs) - Electric Heat
1413
1822
1863
1925
1878
2062
2030
1991
2061
2062
Roofcurb
BAYCURB026B
BAYCURB027B
Unit Cabinet Size
B
C
C+
Filters(f) - Type Furnished
(f) Optional 2” MERV 8 and MERV 13 filters also available.
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Throwaway
Number Size Recommended
Downflow
(2) 20x20x2
(4) 20x25x2
(4) 20x20x2
(4) 20x25x2
(4) 20x20x2
(4) 20x25x2
(4) 20x20x2
(4) 20x25x2
(4) 20x20x2
(4) 20x25x2
(4) 20x20x2
(4) 20x25x2
(8) 20x20x2
(4) 20x16x2
(8) 20x20x2
(4) 20x16x2
(8) 20x20x2
(4) 20x16x2
(8) 20x20x2
(4) 20x16x2
Horizontal
(2) 20x20x2
(4) 20x25x2
(8) 20x25x2
(8) 20x25x2
(8) 20x25x2
(8) 20x25x2
(8) 20x25x2
(12) 20x20x2
(12) 20x20x2
(12) 20x20x2
(12) 20x20x2
Also See for Trane Voyager 12.5 to 25 Tons
Related Manuals for Trane Voyager 12.5 to 25 Tons
-
Trane Rooftop Systems IntelliPak II 90 to 162 Tons Catalogue
206 pages
-
Trane Rooftop Systems IntelliPak II 90 to 162 Tons Installation and Maintenance Manual
200 pages
-
Trane Rooftop Systems IntelliPak II 90 to 162 Tons Programming Guide
157 pages
-
Trane Rooftop Systems Voyager Commercial 27.5 to 50 Tons Installation and Maintenance Manual
138 pages
-
Trane Rooftop Systems Voyager Commercial 27.5 to 50 Tons User's Manual
2 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons Brochure
8 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons Brochure
8 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons Catalogue
152 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons Catalogue
100 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons Installation and Maintenance Manual
52 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons Installation and Maintenance Manual
44 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons User's Manual
2 pages
-
Trane Rooftop Systems Voyager 12.5 to 25 Tons Quick Reference Guide
2 pages